Concrete Worked Examples

Each example follows the same structure: Given → Load combo → Required → Limit states → AISC ref → Formula → Substitution → Decision → Common mistakes.

Module 21 · ACI 318-19 Chapters 19 and 20

Compute Ec, fr, and yield strain for an RC beam

f'c = 4,000 psi normal-weight concrete (λ = 1.0); rebar Grade 60 (fy = 60,000 psi).

Open module →
Module 22 · ACI 318-19 §9.5 and §22.2

Singly reinforced rectangular beam — design moment check

Rectangular beam b = 12 in., h = 22 in., d = 19.5 in. Reinforcement: 3 #8 bars (As = 3·0.79 = 2.37 in²). Materials: f'c = 4000 psi (β1 = 0.85), fy = 60,000 psi. Factored moment Mu = 165 k·ft.

Open module →
Module 23 · ACI 318-19 §22.5 and §9.7.6.2.2

Stirrup spacing design for a rectangular beam

Rectangular beam bw = 12 in., d = 20 in., f'c = 4000 psi (λ = 1.0), fyt = 60,000 psi. Factored shear at distance d from support Vu = 45 kips. Use #3 U-stirrups (Av = 2·0.11 = 0.22 in²).

Open module →
Module 24 · ACI 318-19 §25.4.2 and §25.5.2

Tension development length of a #8 bottom bar

Bottom #8 bar (db = 1.00 in.) in a beam. f'c = 4000 psi NWC (λ = 1.0), fy = 60,000 psi (Grade 60). Uncoated, adequate cover and spacing.

Open module →
Module 25 · ACI 318-19 §22.4.2 and §25.7.2

Axial capacity of a tied square column

Square tied column 18 × 18 in. (Ag = 324 in²) reinforced with 8 #9 bars (Ast = 8·1.00 = 8.00 in²). Materials: f'c = 4000 psi, fy = 60,000 psi. Ties #3 at spacing s.

Open module →
Module 26 · ACI 318-19 Ch. 7

One-way slab — thickness and reinforcement for a 14 ft span

Interior one-way slab, both ends continuous, L = 14 ft = 168 in. Superimposed dead load DL = 25 psf, live load LL = 50 psf. Materials f'c = 4000 psi, fy = 60,000 psi. Clear cover 0.75 in.

Open module →